Send Message
Guangzhou Xingjin Fire Equipment Co.,Ltd.

High pressure nitrogen inert gas fire suppression system

Product Details:
Place of Origin: China
Brand Name: Xingjin
Certification: CAL,CMA,CNAS,ILAC-MRA,CCC
Model Number: QMD15/80, QMD15/90
Payment & Shipping Terms:
Minimum Order Quantity: 1 set
Price: negotiation
Packaging Details: Plywood outer box with bubble bag or paper
Delivery Time: 10-15 working days
Payment Terms: L/C, D/P, T/T, Western Union, Paypal, Credit card
Supply Ability: 300 sets per month
  • Detail Information
  • Product Description

Detail Information

Cylinder Volume: 80L, 90L Capacity Of Gas: 14.25kg, 16.04kg
Pattern Of Extinguishing: Enclosed Flooding Agent: IG100(100% Pressurized Nitrogen)
Working Pressure: 15MPa Color: Red
High Light:

inergen gas fire suppression system

,

inert gas suppression system

Product Description

High pressure nitrogen inert gas fire suppression system

 

 

Description

 

High pressure nitrogen inert gas fire suppression system

 

IG100 uses 100% pressurized nitrogen, which accounts for 78% of the atmosphere, as the extinguishing agent. Its ozone depletion potential (ODP) and global warming potential (GWP) are zero. The atmospheric retention time is zero without any adverse effects on the environment. It fully integrates the design concept of the fire-extinguishing system in the new era, so that the product successfully has the function of environmental protection and efficient fire-fighting.

 

The characteristics of IG100: protecting the ecological environment of the earth, safety and hygiene do not interfere with vision, no stain caused by extinguishing agent, durable of fire fighting effect. Nitrogen can be separated from the air and produced from a wide range of sources at a cheap charge.

 

 

Parameters

 

 

No. Specification Technical Parameter
1 Working Pressure 15Mpa
2 Device Model QMD15/80 QMD15/90
3 Capacity 80Ltr 90Ltr
4 Filling Capacity of Gas 14.25kg 16.04kg
5 Outside Diameter of Cylinder Φ279mm Φ325mm
6 Height of Cylinder 1578+73mm 1345+60mm
7 Spraying Time ≤10s
8 Max Filling Rate 0.178kg/L
9 Power DC24V/1.6A
10 Nitrogen Pressure of Driving Device 6.0±1.0Mpa(20℃)
11 Condition of Reserving Room for Container temperature: 0~50℃
12 Max Working Pressure 17.2Mpa
13 Min Working Pressure 13.6Mpa
 

 

 

 

Application

 

Computer room, telecommunication room, transformer room, electrical switch and distribution room, generator room, leaching tank, drying equipment, paint spraying booth, electrical instrument room, control center, library, archives, treasure trove of cultural relics, etc.

 

 

Packages

 


We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.

 

High pressure nitrogen inert gas fire suppression system 0

 

Advantages

 

  • Compared with the traditional 15MPa system, the number of fire extinguishing agent cylinders can be saved by 25%-50%.
  • The building area between cylinders is effectively reduced, and the overall occupation and utilization rate of the building are improved.
  • Constant 6MPa low pressure release can reduce the cost of pipeline and pipe fittings.
  • The constant release pressure of 6MPa provides more lasting and effective pressure, and the transmission distance can reach 200 meters.
  • The release of the whole system with low pressure can only have a less impact on personnel on sites, equipment and building structure and it is more safety.
  • The external constant pressure reliever can only bear the pressure when the system is spraying, which is convenient for dis-assembly and maintenance and effectively reduces the failure rate of the system.
  • After spraying, the system does not need to replace any parts, simple dis-assembly and secondary filling, the system can be quickly put into operation.
  • The opening area of the pressure-relief device is reduced. the input cost of the pressure-relief device is directly reduced, and the safety buckle is installed and arranged more simply.
  • Nitrogen fire extinguishing system(IG-100) can be widely used to make rapid response to fire, protect staffs on sites, sudden fire, important places sensitive to chemical reaction and effectively protect the safety of personnel and property.

 

 

 

 

Mimic Diagram

 

 

Multiple cylinders for multiple zones

 

High pressure nitrogen inert gas fire suppression system 1

 

 

Multiple cylinders for one zone

 

High pressure nitrogen inert gas fire suppression system 2

Get in touch with us

Enter Your Message